Fault diagnosis and elimination of heat-conducting oil furnace

  

The fault phenomenon The cause of the problem Elimination method
Temperature difference between inlet and outlet oil of heat-conducting oil furnace exceeds given value (determined by experiment and operation)

Circulating pump oil supply decreased

Overload operation

The thermal oil furnace does not match the heating equipment

Insulation bad

Oil contains gas and steam

Eliminate oil pump and pipeline faults

Reduce to normal operation

Reasonable selection of thermal oil furnace

Check the insulation condition and re-insulation if necessary

Continue to degas and steam

The air hammer sound was found in the oil pipe, and the pointer of the pressure gauge was swinging at the inlet and outlet Add the new oil into the air, not off Boil oil with fresh oil
Low level alarm for expansion tank Pipeline system (including oil furnace) failed to timely replenish oil after oil leakage and degassing

Eliminate system defects

New oil supplement

The pressure difference is lower than the given value

The circulation pump is empty

The heat conducting oil contains gas

High filter resistance

Oil leakage in thermal oil furnace tube

Eliminate oil pump and pipeline defects

Perform cooking oil degassing

Cleaning filter

Check heating coil in furnace




If the pipeline oil circulation is not smooth, the possible reason is that the thermal oil furnace filter is blocked, the thermal oil viscosity increases, the valve is not fully open, there are sundries in the tube and other reasons, can be through cleaning the thermal oil furnace filter, add or replace the thermal oil, open the thermal oil furnace valve to remove sundries in the tube and other measures to solve!